* Product Overview
A system that utilizes the external air for the heat pump to provide heating and hot water
* Features
① Simplified system which does not require a waste heat recovery device
② Facilitating up to 70˚C of the water temperature by applying a new refrigerant (IAW Series)
③ Controllable temperature of the output water and stable system by applying the inverter system
④ Enabled to store hot water in the thermal storage tank thereby offering not only the cooling but also the heating functions in winter (IACH Series)
⑤ Simplified system enabling auto control and easy operation
* Application
① Any sector requiring hot water and heating including Hotel, Motel, Dormitory, Hospital, Restaurant (IAW Series)
② Any sector requiring cooling/heating or hot water/cooling /heating (IACH Series)
* Specification of Air Source Heat Pump (IAW-16A series)
|
Model
|
IAW-16A-09
|
IAW-16A-13
|
IAW-16A-17
|
IAW-16A-25
|
|
Capacity
|
Heating
|
KW
|
30.29
|
44.51
|
60.59
|
88.7
|
|
Kcal/h
|
26,053
|
38,275
|
52,106
|
76,279
|
|
USRT
|
8.62
|
12.66
|
17.23
|
25.22
|
|
Power Consumption
|
KW
|
12
|
15
|
24
|
36
|
|
Power Supply
|
3Phase x 380V x 60Hz
|
|
Dimension
|
Length
|
mm
|
2,040
|
2,340
|
2,340
|
3,480
|
|
Height
|
1,240
|
1,340
|
1,570
|
2,000
|
|
Depth
|
710
|
710
|
1,100
|
1,030
|
|
Compressor
|
Type
|
Scroll type
|
|
Quantity
|
1
|
2
|
|
Operation Method
|
Direct-on-line
|
|
Volume Control
|
%
|
0~100%
|
|
Refrigerant
|
Refrigeration Ton
|
RT
|
4.32
|
5.6
|
8.64
|
12.52
|
|
Type
|
R-410A
|
|
Control Method
|
Thermostatic expansion valve
|
|
Condenser
|
Type
|
Brazed Plate type
|
|
Circulation Volume
|
LPM
|
11
|
16
|
22
|
32
|
|
Piping(IN/OUT)
|
A
|
25
|
25
|
40
|
50
|
|
Outdoor unit
|
Type
|
Finned Copper Tube Type
|
|
Thermal Storage Area
|
m2
|
108.5
|
128.2
|
186.5
|
330.3
|
|
Fan & Motor
|
Air
Volume
|
m3/min
|
190
|
240
|
510
|
680
|
|
Size
|
Ø
|
450x3
|
500x3
|
630x3
|
630x4
|
|
Control
|
Temperature Control
|
4way proportional control valve
|
|
Operation Control
|
PCB
|
|
Defrosting
|
Hot Gas
|
Reverse Cycle
|
|
Weight
|
kg
|
350
|
500
|
650
|
750
|
|
Conditions for the products
|
heating
|
Outdoor (DB7°C); Temp of water supply to be 30°C; Temp of output water
to be 70°C, Δ T=40°C
|
■ The above specification may vary depending on the site and temperature conditions.