* Product Overview
An eco-friendly heat pump system that recovers sensible heat from the sea water and supply the recovered heat to the heat/cool the water tank, or produce cold/hot water without using any fossil fuel thereby saving energy and reducing greenhouse gas
* Features
① Significantly saving energy costs associated with heating and cooling of the water tank at eel farms and aquaculture farms
② Maintaining the optimum temperature by accurate temperature control for the growth of the young and live fishes
③ Extended equipment life and easy maintenance with the titanium dual pipe and spiral tube heat exchanger
④ Fitted with the aerification system to the heat source tank so as to generate air bubbles to remove sludge and optimize the heat transfer of the evaporator
⑤ Ability to recover heat even from the low temperature heat source (up to 5°C)
* Application
Applicable to any sector that uses sea water as a heat source and requires hot water and heating/air-conditioning such as Land aquaculture, Mariculture, Offices near the sea shore, Commercial buildings, Motel, Sauna and so on
* Specification of Sea Water Source Heat Pump (IWS-55A, 53A, 13A Series)
|
Model
|
IWS-55A-42
|
IWS-55A-55
|
IWS-55A-62
|
IWS-53A-39
|
IWS-53A-51
|
IWS-53A-76
|
IWS-13A-21
|
|
KITECH
|
IJS-30SE
|
IJS-40SE
|
IJS-50SE
|
IJS-DW140
|
IJS-DW180
|
IJS-DW260
|
IJS-BW75
|
|
Capacity
|
Heating
|
KW
|
147.88
|
191.72
|
216.34
|
137.5
|
180
|
265.5
|
74.5
|
|
USRT
|
42.06
|
54.52
|
61.53
|
39.1
|
51.19
|
75.51
|
21.19
|
|
Cooling
|
KW
|
147.15
|
182.3
|
203.8
|
111.2
|
176.5
|
207.4
|
|
|
USRT
|
41.85
|
51.84
|
57.96
|
31.62
|
50.2
|
58.98
|
|
|
Heating/cooling
|
KW
|
20.0/24.4
|
26.20/32.80
|
34.57/42.94
|
19.68/3237
|
26.68/32.37
|
37.37/42.77
|
21.92
|
|
Power Supply
|
3Phase x 380V x 60Hz
|
|
Refrigeration Cycle
|
Single
|
Dual
|
Single
|
Dual
|
Single
|
|
Dimension
|
Length
|
mm
|
1,950
|
1,950
|
2,200
|
1,950
|
1,950
|
2,600
|
1,950
|
|
Height
|
1,870
|
1,870
|
1,870
|
1,870
|
1,870
|
1,870
|
1,870
|
|
Depth
|
1,900
|
1,900
|
1,900
|
1,000
|
1,000
|
1,000
|
1,000
|
|
Compressor
|
Type
|
Scroll type
|
|
Quantity
|
2
|
1
|
|
Driving Method
|
Y-Δ
|
|
Volume Control
|
%
|
0~100%
|
|
Refrigeration Ton
|
RT
|
12.56
|
16.78
|
21.06
|
21.06
|
16.78
|
12.52
|
19.38
|
|
Refrigerant
|
Type
|
R-410A
|
|
Control Method
|
Thermostatic expansion valve
|
|
Heat
Exchanger
at
Load-side
|
Type
|
Coaxial type
|
Brazed Plate type
|
|
Circulation Volume
|
LPM
|
450
|
500
|
600
|
450
|
500
|
600
|
70
|
|
Piping(IN/OUT)
|
A
|
75
|
100
|
75
|
100
|
50
|
|
Heat
Exchanger
at Heat source-side
|
Type
|
Coaxial type
|
Titanium Tube type
|
|
Piping(IN/OUT)
|
A
|
|
|
|
750
|
600
|
450
|
70
|
|
Control
|
Temperature Control
|
4way proportional control valve
|
|
Operation Control
|
PCB
|
|
Weight
|
kg
|
1,100
|
1,300
|
1,500
|
900
|
1,100
|
1,200
|
600
|
|
Requirements for certified product
|
heating
|
Inlet of heat exchanger at load-side to be 15°C; Inlet of heat exchanger at heat source-side to be 15°C
|
|
cooling
|
Inlet of heat exchanger at load-side to be 25°C; Inlet of heat exchanger at heat-source-side to be 25°C
|
■ Conditions for IWS-13A-21 are water temperature at the inlet of heat exchanger at the heat-source-side to be 15°C; Inlet and outlet of heat exchanger at the load-side to be 45°C and 60°C