A heat pump system that recovers heat from waste water and supplys the recovered heat to the production of cold/hot water and cooling/heating system
* Features
① Production of hot or cold water using waste water discharged from public bath or factory, without any environmental contamination the energy saving system promoted by the nation.
② Much economical than oil or city gas (by 70-50%)
③ Safe system free of risk of explosion that exists with oil and gas
④ Excellent economical system as it utilizes waste heat
⑤ Shorter the term of return on investment compared to other systems
* Application
Applicable to any sector that generates waste water and requires hot water such as Sauna, Golf club, Eel farm, Dyeing factory
* Specifications of Waste Water Source Heat Pump (IWB-12B series)
Model
IWM-12B-34
IWM-12B-38
IWM-12B-51
IWM-12B-67
Capacity
KW
117.79
133.6
180.47
235.7
Kcal/h
101,300
114,900
155,200
202,700
USRT
33.5
38
51.32
67.03
Power Consumption
KW
32
38
50
58
Power Supply
3P * 380V * 60Hz
Compressor Capacity
HP
30
36
48
56
Dimension
Length
mm
1,200
Height
1,940
Depth
760
Compressor
Type
Scroll type
Quantity
2
4
Operation Method
Direct-on-line
Volume Control
%
0~100%
Refrigeration Ton
RT
10.7
12.36
16.48
19.68
Refrigerant
Type
R-22
Control Method
Thermostatic expansion valve
Heat Exchanger at Load-side
Type
Brazed Plate type
Circulation Volume
LPM
52.76
59.84
80.83
105.57
Piping(IN/OUT)
A
40
50
Heat Exchanger
at Heat source -side
Type
Spiral Tube Type
Piping(IN/OUT)
A
125
Control
Temperature Control
Automatic inlet/outlet temperature control
Operation Control
PCB
Weight
kg
450
500
600
680
Operational Condition
Supply side (entry) temp to be 28°C; discharge side (exit) temp to be 60°C; Waste water temp to be 25°C
■ The above specification may vary depending on the site and temperature conditions.
■ The above specification may change without prior notice for further improvement.