A heat pump system that recovers heat from waste water and supplys
the recovered heat to the production of cold/hot water and cooling/heating system
* Features
① Production of hot or cold water using waste water discharged from public bath or factory, without any environmental contamination the energy saving system promoted by the nation.
② Much economical than oil or city gas (by 70-50%)
③ Safe system free of risk of explosion that exists with oil and gas
④ Excellent economical system as it utilizes waste heat
⑤ Shorter the term of return on investment compared to other systems
* Application
Applicable to any sector that generates waste water and requires hot water such as Sauna, Golf club, Eel farm, Dyeing factory
* Specifications of Waste Water Source Heat Pump (IWB-12BA series)
Model
IWB-12BA-62
IWB-12BA-74
IWB-12BA-100
IWB-12BA-117
Capacity
KW
218.6
260
353.02
413.14
Kcal/h
188,000
223,600
303,600
355,300
USRT
62.17
73.94
100.4
117.49
Power Consumption
KW
56
66
88
104
Power Supply
3P * 380V * 60Hz
Compressor Capacity
HP
64
72
96
112
Dimension
Length
mm
1,700
Height
1,940
Depth
1,000
Compressor
Type
Scroll type
Quantity
4
4
8
8
Operation Method
Direct-on-line
Volume Control
%
0~100%
Refrigeration Ton
RT
21.9
24.88
33.76
39.52
Refrigerant
Type
1st
R-22
2nd
R-410A
Control Method
Thermostatic expansion valve
Heat Exchanger at Load-side
Type
Brazed Plate type
Circulation Volume
LPM
74.6
88.73
120.48
140.99
Piping(IN/OUT)
A
40x4EA
50x4EA
Heat Exchanger at Heat source- side
Type
Spiral Tube Type
Piping(IN/OUT)
A
150
Control
Temperature Control
Automatic inlet/outlet temperature control
Operation Control
PCB
Weight
kg
640
770
910
1,050
Operational Condition
Supply side (entry) temp to be 28°C; discharge side (exit) temp to be 70°C; Waste water temp to be 25°C
■ The above specification may vary depending on the site and temperature conditions.