A heat pump system that recovers heat from waste water and supplys the recovered heat to the production of cold/hot water and cooling/heating system
* Features
① Production of hot or cold water using waste water discharged from public bath or factory, without any environmental contamination the energy saving system promoted by the nation.
② Much economical than oil or city gas (by 70-50%)
③ Safe system free of risk of explosion that exists with oil and gas
④ Excellent economical system as it utilizes waste heat
⑤ Shorter the term of return on investment compared to other systems
* Application
Applicable to any sector that generates waste water and requires
hot water such as Sauna, Golf club, Eel farm, Dyeing factory
* Specifications of Waste Water Source Heat Pump (IWH-12A series)
Model
IWH-12A-31
IWH-12AB-35
IWH-12A-48
IWH-12A-55
Capacity
KW
108.41
124.57
169.3
194.53
Kcal/h
93,230
107,130
145,600
167,300
USRT
30.83
35.43
48.15
55.32
Power Consumption
KW
32
38
50
58
Power Supply
3P * 380V * 60Hz
Compressor Capacity
HP
30
36
48
56
Dimension
Length
mm
1,200
Height
1,940
Depth
760
Compressor
Type
Scroll type
Quantity
2
4
Operation Method
Direct-on-line
Volume Control
%
0~100%
Refrigeration Ton
RT
11.2
12.52
17.28
19.84
Refrigerant
Type
R-410A
Control Method
Thermostatic expansion valve
Heat Exchanger at Load-side
Type
Brazed Plate type
Circulation Volume
LPM
37
42.51
57.78
66.39
Piping(IN/OUT)
A
40
50
Heat Exchanger
at Heat source- side
Type
Spiral Tube Type
Piping(IN/OUT)
A
125
Control
Temperature Control
Automatic inlet/outlet temperature control
Operation Control
PCB
Weight
kg
410
510
560
590
Operational Condition
Supply side (entry) temp to be 28°C; discharge side (exit) temp to be 70°C; Waste water temp to be 25°C
■ The above specification may vary depending on the site and temperature conditions.
■ The above specification may change without prior notice for further improvement.