product Image
Low Voltage VFD (Fan and Pump Drive)
Model Name
H100
Series
Inverter (VFD (Smart Automation Solution))
Data
Catalog-LS ELECTRIC-Low Voltage VFD-Drive Solution Catalog
Manufacturer information
provider logo
LS ELECTRIC

Smart Power Solution, Low Voltage, Smart Automation Solution, PLC, Smart Railway Solution, Signaling System and more

Problem with product info?
Update request
Manufacturer
LS ELECTRIC
Brand
-
SKU
133136
Product Name
Low Voltage VFD (Fan and Pump Drive)
Model Name
H100
Size
-
Weight
-
Product Details

 

1. Maximized User Convenience

Communication Module

ㆍRS-485 Capability is built-in

ㆍModbus-RTU, Metasys N2

ㆍBACnet MS/TP is embedded as standard

ㆍLonWorks option can be added

 

Easy to Change Cooling Fan

It is easy to change the cooling fan

without opening the cover of the drive

 

Keypad Exclusive for HVAC

Used to issue commands, configure drive parameters, and for monitoring drive status

ㆍHAND mode (Local, Control, Mode) or AUTO Mode (Remote Control Mode) may be selected.

  - HAND Mode: Used when selecting frequency or run/stop commands.

  - AUTO Mode: Drive operated using the keypad. Multifunctional terminal block and communications.

ㆍFault Status Monitoring

 

 

Specification Level Option (Conduit Kit)

Acquired UL open type & enclosed type 1 certification

  - When the conduit option is used, the drive meets UL Enclosed Type 1 specifications

 

Flange Type

If the space is too small, a heat sink can be installed outside the panel

 

DC Reactor

A built-in DC reactor to improve power factors and reduce THD is installed.

  - DC Reactor built-in as a standard for 400V 37-90kW

 

Built-in EMC Filter

A built-in EMC filter to respond to the specifications for noise reduction

  - 400V 0.75~30kW Built-in as default (C3)

  - 400V 37~55kW Built-in option can be selected (C3)

※ 75~90kW satisfies EMC specifications even without a filter

 

​Compliant​ with Global Specifications

L Plenum Rated (American standards for conditional fire safety)

※ Suitable for installation in compartments handing conditioned air

 

Smart Copier

ㆍPower-free Operation

ㆍLED Feedback

ㆍParameters Read/Write

ㆍEasy to Install

 

Data Flow in Smart Copier

 

2. Efficient Use of Space

Side-by-Side Installation

The size of the control board is significantly reduced when multiple drives are installed by minimizing the distance between products installed

※Side-by-side installation is unavailable for 37~90kW

 

Reduced Size

Main components are optimally deployed through thermal radiation analysis and 3D design to reduce size by 34% compared to iP5A (Volume based)

 

3. Stable System Control

LSLV-H100 drives are intelligent drives equipped with various protective and operation functions for continuous stable operation in response to external environmental changes.

 

Soft Fill Operation

Prevents pump damage caused by extreme pressure change during initial operation of pumps or inside pumps.

 

Start Ramp & End Ramp

Prevents pump damage by changing ramps using the acceleration/deceleration time setting upon initial pump operation

 

Dec Valve Ramp

Prevents pump and pipe damage caused by sudden pressure changes when pumps are stopped or a pump valve is closed, Deceleration time may be set.

 

Multi Motor Control

MMC is used when a single drive is used to control multiple motors in the pump system.

It can control 1 main motor and 5 auxiliary motors.

 

Scheduling (Time Event: Real Time Clock)

Prevents pump damages caused by dramatic pressure changes during initial operation or pumps or inside pumps.

 

Flow Compensation

Compensates for hydraulic loss that occurs when the length of pipes are too long, adding a compensation rate depending on the inverter output frequency.

 

Energy-saving Display (Payback Counter)

Commercial energy consumption is compared to the amount of energy used by the drive to calculate the amount of energy saved.

 

Power-on Resume

When the drive restarts after it was stopped due to power interruption upon communication control, 'Power-on Resume' is used to follow the previous control command.

 

Sleep, Sleep Boost, Wake-up

It is used to put the drive on standby and restarts it using the amount of energy used by the drive to calculate the amount of energy saved.

 

Auto Torque Boost

The drive outputs voltage for the drive by controlling the level of boost to fit the load by itself.

 

Lubrication Control

When a control command is made in the Flow/Oiling Systems, lubrication signals are output for a certain period before the motors are started. Drive control immediately begins form the signal output point until the signals are turned off after the set time

 

Damper Control

When a damper exists in the system configuration, the drive will command the damper to open/close or receive feedback signals for protection.

 

Detection of Pipe Broken

Upon PID operation, pipe damages or leakage is detected to display a warning or a trip.

 

Level Detection

When the drive is operated under a frequency that is beyond the set frequency and source (voltage, current, and etc.) values to be detected are above or below the user set values, it generates a trip or activates a relay for protective operation

 

Pre-Heat

Pre-heats motors by direct current output when the motors are at fixed state of time in order to prevent condensation in the motors

 

Under Load Protection

When running pumps including no flow and dry pumps under the set frequency, the drive issues a warning function and when the trip is generated, free-run, deceleration, or stop can be selected.

 

Macro Setting

If a particular application is selected, frequently used parameters and set values are changed and registered in a macro group.

 

KEB, Kinetic Energy Buffering

Upon loss or momentary interruption of input power, if the KEB is set, the drive maintains a DC Link Voltage using regenerated energy from the motor during the interruption period.

 

Pump Clean

Upon pump operation, the efficiency of pumps may decline when foreign substances are stuck in an impeller. The pump clean removes foreign substances to extend pump life.

 

Aux Motor PID Compensation

Pipe flow increases and conduit pressure decreases as the number of auxiliary motors increases. The 'Aux Motor PID Compensation' is used to compensate pressure loss suitable for the given motor when operating auxiliary motors.

 

Load Tuning

Establishes load (current & power) curves based on drive frequency so as to make load characteristics curve required for 'Under Load' and 'Pump Clean.'

 

Fire Mode

When an emergency such as fire occurs at the suction/exhaust fans, but hardware did not fail nor has a critical defect, the drive is continuously operates to protect other systems under the set frequency and direction.

 

LS ELECTRIC
Smart Power Solution, Low Voltage, Smart Automation Solution, PLC, Smart Railway Solution, Signaling System and more
We open up a brighter future through efficient and convenient energy solutions. We at LS ELECTRIC are leading the power system and automation sectors of the nation’s industry, concentrating all our effort and energy on ‘product quality’ and ‘innovative ideas.’ Under our motto Futuring Smart Energy, we are striving to stay ahead of the competition with our world-class quality and technological prowess, even in this new era of Smart Energy created by the convergence of power systems and automation. In the power systems field we are doing our utmost to expand our share of the global market, particularly in China, the Middle East, and Southeast Asia, while in the automation field we are making a foray into global markets by securing world-class technologies. Furthermore, we have secured a solid position in the smart energy sector [e.g. smart grid, micro grid, energy storage systems (ESS), photovoltaic energy] as a representative company of Korea, and have become the first Korean enterprise to make inroads into the global high-voltage direct current (HVDC) market. Naturally, we have been selected as one of the Top 100 Global Innovative Businesses by Clarivate Analytics for ten consecutive years as a result of our remarkable achievements. We will continue to achieve better results as a business synonymous with first-rate quality and excellent R&D capability, a business that provides total solutions to customers, a business to be reckoned with, and a business that knows how to grow together with its customers.  