| Main Supply |
Main Voltage (L1, L2, L3) - SSC□-□□□-V4 - SSC□-□□□-V6 |
200~440VAC (+10/-15%) 200~575VAC (+10/-15%) |
| Main Frequency (at start) |
45 to 66 Hz |
| Rated Insulation Voltage |
600VAC |
| Form Designation |
Bypassed, Semiconductor Motor Starter form 1 |
Control Voltage (A1, A2, A3) |
SSC□-□□□-□□-C1 |
110~240VAC (+10%/-15%) |
| SSC□-□□□-□□-C1 |
380~440VAC (+10%/-15%) |
| SSC□-□□□-□□-C2 |
24VAC/VDC((±20%) |
| Current Consumption (During Run) |
< 100mA |
Current Consumption (Inrush) - SSC□-□□□-□□-C1 - SSC□-□□□-□□-C2 |
10A 2A |
| Inputs |
Start (Terminal 01) |
Normally open (150kΩ@300VAC and 5.6kΩ@24VAC/VDC) |
| Stop (Terminal 02) |
Normally Closed (150kΩ@300VAC and 5.6kΩ@24VAC/VDC) |
| Outputs |
Main Contactor (Terminals 13,14) |
Normally Open (6A, 30VDC / 6A, 250VAC Resistive) |
Programmable Relay (Terminals 23,24) |
Normally Open (6A, 30VDC / 6A, 250VAC Resistive) |
| Environmental |
Degree of Protection SSC□-018 to SSC□-060 |
IP20 |
Degree of Protection SSC□-075 to SSC□-200 |
IP00 |
| Operating Temperature |
-10°C to +60°C |
| Storage Temperature |
-25°C~60°C (to +70°C for Less than 24 Hours) |
| Humidity |
5%~95% Relative Humidity |
| Pollution Degree |
Pollution Degree 3 |
| Vibration |
IEC 60068 Test Fc Sinusoidal 4Hz to 13.2Hz : ±1mm Displacement 13.2Hz to 200Hz : ±0.7g |
| EMC Emission |
Equipment Class (EMC) |
Class B |
| Conducted Radio Frequency Emission |
0.15MHz to 0.5MHZ: <56~46dB (uV) 0.5MHz to 5MHz: <46dB (uV) 5MHz to 30MHz: <50dB (uV) |
| Radiated Radio Frequency Emission |
30MHz to 230MHz: <30dB (uV) |
| EEMC Immunity |
Electrostatic Discharge |
4kV Contact, 8kV are Discharge |
| Radio Frequency Electromagnetic Field |
0.15MHz to 1000MHz: 140dB(uV) |
| Rated Impulse Withstand Voltage (Fast Transients 5/50ns) |
2kV Line to Earth, 1kV Line to Line |
| Voltage Dip and Short Time Interruption |
100ms (at 40% Nominal Voltage) |
| Harmonics and Distortion |
IEC 61000-2-4 (Class 3), EN/IEC61800-3 |
| Short Circuit |
Rated Short-circuit Current SSC□-018 to 060 |
5KA* |
| Rated Short-circuit Current SSC□-075 to 200 |
10KA* |
| Heat Dissipation |
During Start |
3 watts / Ampere |
| During Run |
10 Watts Typical |
| Operational Life |
SSC□-018 to 060 |
1,000,000 Operations |
| SSC□-075 to 200 |
30,000 Operations |