product Image
170kV Gas Insulated Switchgear
Model Name
-
Series
Switchgear
Data
-
Manufacturer information
provider logo
DONGNAM

Nonferrous metal casting and electrical equipment, Fitting, Filling machine, Aluminum for gas reduction switching device and more

Problem with product info?
Update request
Manufacturer
DONGNAM
Product Type
Machine
Brand
-
SKU
55870
Product Name
170kV Gas Insulated Switchgear
Model Name
-
Size
-
Weight
-
Product Details

DONGNAM 170kV Gas Insulated Switchgear

 

Product Specification

Name of Product

170kV Gas Insulated Switchgear (GIS)

Rated Voltage(kV)

170

Applied Standard GIS

ES 6110-0002 / IEC 62271-203

CB

IEC 62271-100

Rated Current(A)

1,250 / 2,000 / 3,150/4,000

Rated Breaking Current(kA)

50

Power Frequency Withstand Voltage(kV) /
Disconnector with Surge Protection Gap

325 / 375

Lightening Impulse Withstand Voltage(kV) /
Disconnector with Surge Protection Gap

750 / 860

Rated SF6 GAS Pressure
(Mpa. G)

at cutoff part

0.6

et cetera

0.6

Circuit Breaker's Service Classification (Class)

E1 / C2 / M2 / S2

Control Method

circuit breaker

3 phase oil pressure control

disconnector

3 phase Electric Spring Operator / Electric Operator

earthing switch

3 phase Electric Spring / Manual Operator Method

DONGNAM
DONGNAM
Nonferrous metal casting and electrical equipment, Fitting, Filling machine, Aluminum for gas reduction switching device and more
Inquiry