| Item |
Criteria |
Measured Data |
Results |
| Visual Inspection |
w355 x d655 x h800 ±5mm |
- |
Passed |
| Output Voltage Regulation |
100VAC ± 2% @0%, 50%, 100% Load |
0.01% |
Passed |
| Output Frequency Regulation |
60Hz ± 0.5% @0%, 50%, 100% Load |
-0.47% |
Passed |
| Efficiency |
min. 85% @ 100% Load |
87.64% |
Passed |
| Input Current THD |
max. 85% @ 100% Load |
4.37% |
Passed |
| Output Voltage THD |
max. 3% @ 0%,50%, 100% Load |
1.64% |
Passed |
| Step Load Test |
Step Load : 50% -> 100%
- Transient Voltage : ±5%
- Recovery Time : within 50ms |
-1.14%
3ms |
Passed |
| Power Failure / Restore Test |
- Transient Voltage : ±5%
- Recovery Time : within 50ms |
1.14%
6ms |
Passed |
| Transfer Time Test |
Within 4ms |
0.9ms |
Passed |
| Audible Noise |
62dBA @ 1.5m distance |
61dBA |
Passed |
| Battery Current Limitation |
5.0A ± 1.0A |
5.7A |
Passed |
| ESS Operation Mode Test |
Mode 1. Battery(Charge) Mode |
Rectifier + Battery Charge |
Passed |
| Mode 2. Commercial & PV Power Mode |
Rectifier + PV Charge |
Passed |
| Mode 3. PV & Battery(Discharge) Mode |
PV Charge + Battery Discharge |
Passed |
| Mode 4. Battery(Discharge) Mode |
Battery Discharge |
Passed |
| Mode 5. Commercial Power Failure Mode |
Battery Discharge + PV Power |
Passed |