| Inputs: |
Display: |
| Universal Input |
Backlit LCD rotatable to any angle |
| Thermalcouple |
Display Function: |
| T/C (K, S, B, E, J, T, R, N)...... |
5 Digits programmable & 0-100% Bargraph |
| RTD |
Display Unit: |
| CU50 / PT100, 2/3/4 wire...... |
oC / oF / oR / oK |
| mV |
Setting Method: |
| -128 to +128mV / -1000 to +1000mV...... |
B Type |
| Resistance |
USB+PC software (windows system£© |
| 0-600 / 0-5000 |
C Type |
| Accuracy: |
HART signal |
| +/- 0.1% of span |
D Type |
| Stability: |
HART signal & keypad |
| +/- 0.1% of span for 2 years |
Current Output: |
| Temperature Effect: |
4 - 20 mA 2 wires with HART Signal |
| +/- 0.1% of span per 10 oC |
Load |
| CJC compensation: |
Rohm = (Vdc-9) x 50 |
| +/- 0.5 oC |
Power Supply: |
| Simulation Output: |
9 ~ 36 VDC |
| 4-20 mA |
Digital Communication: |
| Material: |
HART Protocol |
| Wetted Parts |
Cable Entry: |
| SUS304 / SUS316 / Has. C / Tantalum etc |
M20 Conduit Threads / 1/2" NPT (Female) |
| Housing |
Damping: |
| Low copper aluminum alloy (Sprayed with |
0 - 32 seconds |
| light blue polyurethane paint) |
Response Time: |
| Module Housing |
100 mS |
| Flame-resistant PC |
Turn on Time: |
| Name / Tag Plate |
2 Seconds with minimum damping |
| Stainless Steel 304 / Stainless Steel 316 |
Zero Calibration: |
| Process Connection: |
Automatic zero calibration by press-button |
| Threads / Flanges |
Isolation: |
| Over Temp. Limit: |
Input/Output/GND isolated to 480VDC |
| 120% of Full Scale |
Power Supply Effect: |
| Mounting: |
+/-0.005 of Span per V |
| Direct mounting or bracket on 2" Pipe |
Weight: |
| Humidity Limit: |
60g (Converter only) with display |
| 0 to 100% Relative Humidity |
30g (Converter only) without display |
| Ambient Temperature: |
Protection Class: |
| -25 to +85 oC |
IP67 (Standard) |
| Vibration Effect: |
Intrinsically Safe EEx ia IIC T5 (Standard) |
| +/-0.05% of URL per g to 200 Hz in any |
Explosion proof Ex D IIB T5 |
| axis |
Sensor Connection: |
| EMI / RFI Effect: |
M27*2 (Female) |
| Follow SAMA PMC 33.1 from 20 to 1000 |
|
| MHz and for field strengths up to 30 V/m |