The EHV+ Series is a fully IEC61131-3 compliant PLC Series which offers effective programming features and reduced debugging and commissioning time.
CPU module "EHV+"
The powerful hardware performances of existing EHV Series are succeeded to EHV+, such as multi-programming port (USB, Ethernet, Serial), compatibility of I/O modules for EH-150 Series, high reliability, superior in quality and much more.
Scalable memory size (2 Models)
EHV-CPU1025 (512KB) EHV-CPU1102 (2,048KB)
Integrated Development Environment (IDE) "HX-CODESYS"
HX-CODESYS is a professional development tool based on CODESYS V3.5 by 3S. Compared to standard CODESYS, following components are additionally included in the installation file(setup.exe)
- Device description files (.xml) for EHV+ Series - Special libraries for EHV+ Series. (get_error_info, Counter_interface, etc.)
Standardized programming style with 5 programming languages (LD, FBD, IL, ST, SFC).
No need to study manufacturer’ s specific programming way.
Easy to start using Hitachi PLC for those who having; No experience of PLC Experience of other manufacturer’s programming Experience of high level languages
Same Variable names are shared by PLC, HMI, SCADA, and other I/O devices.
Offline simulation function on programming software.
General Specifications
Irem
Specification
Operational temperature
0 to 55℃
Storage temperature
-10 to 75℃
Operational humidity
5 to 95% RH (no condensation)
Storage humidity
5 to 95% RH (no condensation)
Vibration resistance
Conforms to IEC 60068-2-6
Noise resistance
Noise voltage 1,500 Vpp, Noise pulse width 100 ns, 1 µs (Noise input by a noise simulator across input terminals of a power module according to measuring method of Hitachi-IES.)
Based on IEC 61131-2 (not applied for input modules)
Static noise 3,000V at electrode part
Certifications
CE, RCM
Insulation resistance
20MΩ minimum between AC terminal and frame ground (FE) terminal (based on 500V DC megger)
Dielectric withstand voltage
1,500V AC for 1 minute between AC input terminal and frame ground (FE) terminal
Ground
Class D grounding (grounding with the power supply module)