MCB is applicable to electric circuit with rated voltage 230/400V, 240/415V AC, frequency 50/60Hz and rated current is up to 63A. The product provides against overload and short circuit and equipments in household and commercial installations. MCB is also used as non-frequent changeover of electric circuit.
Line-Up
BK63 series
BTK63 series
Alarm switch (for BK63)
Auxiliary switch
Tripping Characteristics
Type B Instant tripping characteristics : 3–5In Application : computers and electronic equipments
Type C Instant tripping characteristics : 5–10In Application : general load such as bulbs , motors
Type D Instant tripping characteristics : 10–20In Application : high current surge device such as transformers, motors with heavy load
Colored Handles
Easy to distinguish the rated current of the MCB by means of colored handle.
1A
Black
20A
Blue
2A
Pink
25A
Yellow
3A
Pink
32A
Purple
4A
Brown
40A
Black
6A
Green
50A
White
10A
Red
63A
Cupper-colored
16A
Grey
Approval
CE marking
CB Certifi cate
Rating and Specifications
Type
BK63
BTK63
Protection
Overload and short circuit
Rated current
1, 2, 3, 4, 6, 10, 16, 20, 25, 32, 40, 50, 63A
Characteristics
B, C, D curve
Number of poles
1P, 1P+N, 2P, 3P, 3P+N, 4P
Breaking capacity
1P
2, 3, 4P
1P
2, 3, 4P
6kA at 230/400VAC
6kA at 400VAC
10kA at 240/415VAC
10kA at 415VAC
Standards
IEC60898
Approval
SEMKO CB scheme
KEMA CB scheme
Type of trip
Thermal magnetic release
Electrical endurance
6,000 operations
8,000 operations
Installation
35mm DIN rail
Width
17.8mm per pole
Type of terminal
Lug type (Cable up to 25mm2)
Alarm switch (Optional)
1changeover contact 6A at 230VAC,3A at 415VAC(AX) 6A at 230VAC,3A at 415VAC(AL) 2A at 48VAC,1A at 125VAC Lug terminal Cable capacity 2.5mm2 9mm wide