GENERAL FEATURES
Important loads hospitals, commercial buildings, government offices, Olympic stadiums, water pumping station, etc.
- Non-SF6, solid insulation, vacuum circuit breaker with three position disconnecting switch
- Ultra-high fast source transfer (with in 6 cycles)
- Tee-off circuit protection
- Three transfer mode – Ultra fast, fast, Normal mode
- Prefer, non-prefer mode selection
- Retransfer mode (open transition and close transition)
- All in one, μ-processor control
- TU function – DNP 3.0 protocol with TCP/IP connection port
- Protection relay
TECHNICAL DATA
| Description |
SICB-26 |
| Rated Maximum Voltage |
25.8 kV |
| Rated Continuous Current |
600 A |
| Speed of source transfer from voltage sag |
Within 5cycle |
| Making Current |
12.5 kA |
| Power Frequency Withstand Voltage |
60 kV |
| Impulse Withstand Voltage |
125 kV |