Quick menu gives easy access to the most frequently used parameters
DIN-Rail Mountable
Side-by-Side Installation (2mm between drives)
Built-in Potentiometer
Easy to connect the peripherals
Easy to connect the peripherals
Smart Copier Connection with RJ45
Remote Keypad Connection with RJ45
PC connection with Drive View7 SW control and monitoring system
3. Global Standard Compliance
Contactors
Specification
LSLV M100-EOFN
0001
0002
0004
0008
0015
0022
Applied motor
Heavy duty
HP
0.125
0.25
0.5
1.0
2.0
3.0
kW
0.1
0.2
0.4
0.75
1.5
2.2
Rated output
Rated capacity [kVA]
0.3
0.6
0.95
1.9
3.0
4.5
Rated current [A]
0.8
1.4
2.4
4.2
7.5
10.0
Rrequency [Hz]
0~400Hz
Voltage [V]
3 phase 200-240V
Rated input
Voltage [V]
1 phase 200~240Vac(-15% to +10%)
Frequency [Hz]
50~60Hz(±5%)
Rated current [A]
1.0
1.8
3.7
7.1
13.6
18.7
Cooling type
Natural cooling
Forced fan cooling
Weight (Kg)
0.66
1
1.45
Environment
Environment
Ambient temperature 1)
-10 ~ 50℃(14 ~ 122℉), Ambient temperature under the condition of no ice or frost
Ambient humidity
Relative humidity less than 95% RH(to avoid condensation forming)
Storage temperature
-20 ~ 65℃(-4 ~ 149℉)
Surrounding environemt
Prevent contact with corrosive gases, inflammable gases, oil stainsk dust, and other pollutants(Pollution Degree 2 Environment)
Altitude/Oscillation
Maximum 1000m above sea level for standard operation. / 9.8m/sec2 (1G) (From 1000 to 4000m, the rated input voltage and rated output current of the drive must be derated by 1% for every 100m.)
Pressure
70 ~ 106 kPa
*1) 01 ~ 0.2kW products can be operated at a maximum of 50℃.
However, the lifespan of the product maybe reduced when operating continuously with a full load when the ambient temperature exceeds 40℃