- 3-phase SF6 gas insulated vacuum interruption auto circuit recloser for pole mounted or substation applications
- Integrated line sensors, vacuum interrupters, solenoid dual latch mechanism, dead line operation module and microprocessor based R6 relay to provide reliable operations without maintenance
- Certified in accordance with ANSI C37.60 (1981)
- RTU based μ-processor control
- Sef, Hif and open conductor fault protection
- Enhanced loop operation
TECHNICAL DATA
Description
SMRC-15
SMRC-26
Rated Maximum Voltage
15.5 kV
27 kV
Rated Continuous Current
630 A
630 A
Power Frequency Withstand Voltage (dry -1min / wet -10sec)
50 kV / 45 kV
60 kV / 50 kV
Lightening Impulse Withstand Voltage (BIL)
125 kV
150 kV
Rated Fault Making Capacity (peak)
52 kAp
32.5 kAp
Rated Short Circuit Interrupting Current
20 kA
12.5 kA
Mechanical/Electrical Operations
10,000 times
10,000 times
GENERAL FEATURES
- Polymer recloser with hydrophobic cycloaliphatic epoxy.
- Bi-stable magnetic actuator that enables maintenance-free and more reliable operation by eliminating components.