SHN-2000 accepts pulse and totalize the input values in an isolated condition.
ㆍIt also contains back up function; it memorizes the indication values of power failure before state.
ㆍExternal reset terminal is placed on back side of the unit.
ㆍToo easy to read, taking high bright red FND.
ㆍOutput 1:1, 10:1, 100:1 pulse.
Products Detail
| SHN-2000 |
| INPUT |
OUTPUT |
POWER |
| Dry Contact |
Pulse (O.C) |
AC 110V/220V (50~60Hz) |
| Open collector |
|
|
| Voltage Pulse |
|
|
Technical Data
| Power Supply |
AC110/220V Internal selection 60Hz ±10%
Power Consumption Approx. 5VA
|
Input |
Dry Contact OR Open collector OR Voltage Pulse |
| Accuracy |
0.15% Full scale, ±1 Digit (25℃ ±5℃) |
Sampling Cycle |
100msec |
| Analytic Capacity |
15bit |
Lineality |
±0.02% Full scale |
| Temp Coefficient |
± 0.015%℃ |
Moment Flow Range Value |
9999 |
| Max Conting Value |
0~999999 |
Tatal Integrate Value |
0~9999999 |
| Insulation Resistance |
Greater than 100MΩ whit DC500V |
Dielectric Strength |
Input-Power AC2000V
Output-Power AC1000V
GND Power AC1000V
|
| Operating Temperature / Humidity |
-20~60℃ / 90%(N.C) |
Storage Temperature / Humidity |
-20~80℃ / 95%(N.C) |
| Dimensions |
W96 * H48 * D112 (mm) |
Case Material |
ABS Resin(white) |
| Weight |
About 450g |
Mounting |
Panel mounting |