SHN-ARR30/70R is Designed for DC signal line including 2-wire transmitters.
It absorbs the lightning surges that are transmitted in the DC signal wiring to insure the line potential will remain at a low voltage to prevent damage to electronic components.
The unit is designed not to fall in the short-circuit condition, thus protecting the equipment form any damage caused by short circuits.
ㆍ2 stage protect construction
ㆍApplied technique : Basis on ANSI / IEEE Category "A" / "C", IEC Category C1, C2, C3, D1
ㆍSurge Suppression Voltage : under 30V (p-p)
Products Detail
| SHN-ARR30-R Series |
| APPLICATIONS |
서지 또는 서지로부터 측정 환경 측정 기기 보호 |
CERTIFICATE |
UL, CE, CSA |
PROTECTION FUNCTION |
Thermal & Short Circuit Fuse, 2-Stage Surge Protect Noise Filtering (EMI/RFI) |
| APPLIED TECHNIQUE |
BASE ON ANSI/IEEE Category “A”/”C |
FOR USE |
4~20mA/(DC24V) SIGNAL LINE |
MOUNTING |
Rail Mounting type(Plug in type) |
| MAIN PROTECT MATERIALS |
MOV(Metal-oxide varistor) |
Technical Data
| Mode |
SHN-ARR30-1R OR SHN-ARR30-2R OR
SHN-ARR30-3R OR SHN-ARR70-1R
SIGNAL(DC24V/4~20mA)
|
Nominal voltage |
24V/DC |
| Rated voltage |
26VDC OR 28VDC OR 30VDC OR 68~70VDC |
Nominal Discharge current(Mode:8*20μsec) |
10KA |
| Max Discharge current(Line:8*20μsec) |
20KA |
Response time |
1nsec or less |
| Clamping Voltage Rating |
43V(p-p) |
Insulation Resistance |
1000MΩ |
| Capacitance |
1700pF(1MHz |
Nominal load current / Rated current |
100mA / 2A (60℃) |
| Voltage protector level Up |
55V |
Max, Operating current(Leakage current) |
25μA |
| Temperature range |
-40℃ to + 80℃(±5℃) |
Ip code |
IP20/NEMA12 |
| Dimension(mm) |
W23.5xH90xD62(mm) |
Case material |
ABS |
| Weight |
150g |
Mounting |
Din Rail Type(Plug in type) |