Converting an alternating current that receives from a CT-sensor into a standard process signal.
ㆍMonitoring of power line and power supply current centralized monitoring and controlling of motor pumps or heaters by DCS.
ㆍTure R.M.S sensing.
ㆍ1 or 2 outputs are available from 1 input.
ㆍContains overvoltage protection circuit.
ㆍTransformer isolation type.
Product Detail
| SD-AVC |
| INPUT |
OUTPUT1 |
OUTPUT2 |
POWER |
| AC 0-1A |
0-10V |
0-10V |
AC95~250V_50~60Hz |
| AC 0-5A |
0-5V |
0-5V |
|
| |
0-1V |
0-1V |
|
| |
1-5V |
1-5V |
|
| |
4-12mA |
4-12mA |
|
| |
0-20mA |
0-20mA |
|
| |
12-20mA |
12-20mA |
|
| |
4-20mA |
4-20mA |
|
| |
Other |
Other |
|
Technical Data
| Model |
SD-Series |
Function |
Transmit DC signal in isolated conditon |
| Input |
mA, RTD, 2-Wire, Potentiometer, T/C, Pulse, CT, PT |
Output |
DC Siganl (4-20mA, 1-5V) Max : 2ch |
| Power |
AC 95~250V |
Accuracy |
0.1% / Full scale |
| Display |
LCD |
Response Time |
0.5 sec (0~90%) |
| Front Adjustment |
Zero and Span 5% |
Weight |
About 200g |
| Mounting |
Din Rail mounting |
Dimensions(mm) |
W34 * H105 * D 100 |