Chat with us, powered by LiveChat FLEX Power Regulator | PARA ENT - Komachine
Product Name FLEX Power Regulator
Model FLEX-Type
Series Power Regulator
Catalog
Product Description

- Read and write function through EtherCAT communication.

- Improving power factor Distributing momentary maximum output power by sequential control through synchronization, when multiple power regulators are operated at the same time.

- Possible to read and write through PSD(PARA SMART DISPLAY) or communication function. And with just one PSD, every parameter and alarm can be selected for multiple FLEX.

- To detect partial load failure in multiple parallel loads.

- To realize detecting partial load failure immediately and precisely through PARA-ENT its own unique auto-tuning function.


      





Feature



SMART MPD (Max Power Distribution) Function

- Improving power factor Distributing momentary maximum output power by sequential control through synchronization, when multiple power regulators are operated at the same time.


SMART Communication

- EtherCAT READ&WRITE

- RS-485 2 Wire half-duplex

- MODBUS(RTU),Baud rate MAX: 115,200bps


SMART PLF (Partial Load Failure)

- To detect partial load failure in multiple parallel loads.

- To realize detecting partial load failure immediately and precisely through PARA-ENT its own unique auto-tuning function.


Alarm history

- Last 6 alarms are saved to check out type of alarm easily.

- Even main power is cut off by alarm function, alarm history is saved for better maintenance and user’s convenience.


Convenient parameter setting by PSD

- All parameters and alarms are selected by PSD or RS-485 communication.

- Through selecting parameters and alarms, the usage can be optimized at different circumstances.

- Multiple FLEX products under the same condition and same rated current, all parameters and alarms can be selected with only one PSD using COPY&PASTE function. This is to save time and money. And if you connect PSD to any of FLEX product, you can check out the status of product immediately.


SMART SELF-DIAGNOSIS

- Self diagnosis to check parameter setting, alarm setting and all the wiring status for user’s convenience.


SMART TEST

- When actual load is hardly tested, user can test with small load allowing output arbitrarily.





Ordering Code


① TYPEFLEX
② Rated Voltage1 : 110VAC    2 : 220VAC    3 : 330VAC    4 : 440VAC    5 : 550VAC   
③ Rated Current025 : 25A    040 : 40A    055 : 55A    070 : 70A    090 : 90A    110 : 110A    130 : 130A    160 : 160A    200 : 200A
④ WIRING1P3L : Three shingle phase    3P3L : One three phase
⑤ PSD(Option)PSD : With PSD    NONE : Without PSD
⑥ RS-485(Option)RS : With RS-485    NONE : Without RS-485
⑦ EtherCAT(Option)E : With EtherCAT    NONE : Without EtherCAT
⑧ MPD OptionMPD : With MPD    NONE : Without MPD





Specification

ModelFLEX Power Regulator
Rated Voltage110V / 220V / 380V / 440V
Allowable Voltage Difference±10% of Rated Voltage
Rated Current25A ~ 200A
Frequency50/60Hz Auto detect
Minimum Load1A
Output Range0 ~ 94%
PCB PowerDC 24V
Power consumptionMax. 13W (Fan included)
Input signal4~20mA(Default) 3CH / 0~5V, 1~5V, 0~10V(Option)
AlarmN.O. (2ch, Ic ≤ 1A)
Digital input1ch
Control methodPhase-Angle(current F/B) / Zero-Crossing(MPD Function: Option)
Withstand Voltage2.3KVAC (Step 1Min)
Insulation resistance220MΩ
CoolingCooling fan basically installed
AlarmOver Current, Over Temperature of heatsink(60℃, 80℃), Fuse failure, Load Failure, SCR failure Main power failure(No alarming, LED display), FAN alarm, Partial load failure. Unbalanced load
Ambient Temp0~40℃
Humidity40~85%RH (No condensation)
CommunicationEtherCAT Slave (Option), RS-485 (Option)
Display3 Color LED (1EA Pilot, 1EA/Each Channel)
Net WT.25A~70: 4.2Kg / 90~200A: 9.0Kg