PLC MASTER-K Series

모델명

시리즈

PLC (Smart Automation Solution)


구매 안내

아래는 참고용 정보이므로 세부 조건은 반드시 제조사/판매자에게 문의 바랍니다.

결제 방법

제조사/판매자에게 문의 바랍니다.

납기 정보

제조사/판매자에게 문의 바랍니다.

배송 정보

제조사/판매자에게 문의 바랍니다.

원산지

제조사/판매자에게 문의 바랍니다.


1544-2080

제품 상세 설명

K120S

Powerful & compact block-type PLC CPU, digital I/O and power part are embedded in block-type PLCs, which is very compact and easy to install in area you want for system configuration. Through various built-in function, the user can configure a cost-effective system.

 

Features

K80S Features

Compact and high-function block type

ㆍBase: 10, 20, 30, 40, 60 points
ㆍExpansion: 10, 20 points

 

Various built-in functions for applications

ㆍHSC 1 point, Pulse output 1 point

ㆍPID (Max. 8 loops), Pulse catch 8 points

ㆍBuilt-in RS-232C I/F 1Ch: 4 (Rx), 7 (Tx), 5 (SG)

 

Various applications with special/comm. modules

ㆍAnalog input/output: G7F-ADHA

ㆍAnalog input: G7F-AD2A

ㆍAnalog timer: G7F-AT2A

ㆍCnet I/F: RS-232C, RS-422

ㆍFnet (Master)/Rnet (Master)

ㆍProfibus-DP (Slave)/DeviceNet (Slave)

ㆍRTC/Memory pack

On-line edit in KGL WIN

 

K120S Features

High-performance and various block type

ㆍEconomic type: 10/14/20/30 points (10/14 points: 2points built-in Analog Timer)

ㆍStandard type: 20/30/40/60 points

ㆍVarious expansion modules: input, output, mixed modules

ㆍP area extended for SMART I/O application (P000~P63F)

ㆍHigh-speed processing speed: 0.1㎲/step (standard type)

ㆍBattery-less backup
  - Program backup: EEPROM backup while online editing
  - Data backup: Super capacitor

ㆍVarious input handing: Input filter, pulse catch

 

Enhanced communication functions

ㆍBuilt-in RS-232C (Ch0) and RS-485 (Ch1) support *1)

ㆍTransmitting data monitoring support: KGLWIN

ㆍVarious option modules
  - Cnet (RS-232C, RS-422) Fnet/Rnet (master module)
  - Profibus-DP/DeviceNet (slave module)

 

Powerful built-in functions

ㆍHigh-speed counter: 32-bit signed operation
  - Counter range: -2,147,483,648 ~ 2,147,483,647
  - Function: ring counter, latch counter, comparison (equal/zone/task), RPM

ㆍPositioning function (DRT/DT type)
  - Control axis: 2 axes (100kHz)
  - Operation method: single, repeat
  - Operation mode: end, keep, continuous
  - Additional functions: return to origin, JOG operation, PWM output

ㆍPID operation function
  - Relay/PRC auto-tuning, SV ramp, delta MV, PWM output, position/velocity algorithm

 

Various expansion modules

ㆍ7 Digital I/O modules: G7E-DR(08/10/20)A, G7E-TR10A, G7E-DC08A, G7E-RY(08/16)A

ㆍ9 Analog I/O modules: G7F-ADHA(B/C), G7F-AD2A(B), G7F-DA2I(V), G7F-AT2A, G7F-RD2A

ㆍ6 Comm. modules: G7L-CUEB(C), G7L-DBEA, G7L-PBEA, G7L-FUEA, G7L-RUEA

ㆍ2 Option modules: G7E-RTCA, G7M-M256B

 

Specification

K80S System Specifications

Item Specifications
Operation method Cyclic execution of stored program, Time-driven operation, Interrupt task execution
Program language Mnemonic, Ladder
I/O control method Scan synchronized batch processing method (Refresh method), Direct method by program
Number of instructions Basic 30
Application 218
Processing speed 0.5㎲/Step
Program memory capacity 7Ksteps
Memory device P (I/O Relay) P0000~P31F (512 points)
M (Auxiliary relay) M0000~M191F (3,072 points)
K (Keep relay) K0000~K031F (512 points)
L (Link relay) L0000~L063F (1,024 points)
F (Special relay) F000~F063F (1,024 points)
T (Timer) 100ms T000~T191 (192 points)
10ms T192~T255(64 points)
C (Counter) C000~C255 (256 points)
S (Step controller) S00.00~S99.99 (100 x 100)
D (Data register) D0000~D4999 (5,000 words)
Timer type ON Delay, OFF Delay, Integration, Monostable, Retriggerable timer
Counter type Up, Down, Up-Down, Ring counter
Self-diagnosis functions Watchdog timer, Memory error, I/O error, Batter error, Power supply error
Built-in special function PID control Controlled by instruction, Auto tuning, Forward/Reverse action, Forced output, Operation scan time setup
Cnet I/F function (RS-232C) Dedicated protocol, MODBUS protocol, User-defined protocol
High speed counter Counting speed 1 Phase: 16kHz (1 channel)
2 Phase: 8kHz (1 channel)
3 Counting modes
Counting method 1Phase, up/down count with program Input
1Phase, up/down count B-phase Input
2 Phase, up/down with phase difference
Multiplication 1, 2 or 4
Pulse catch Pulse width : 0.2 ms, 8points
Pulse output 2kHz
External interrupt 8 points (0.4ms)
Input filter 0~15ms (Setting by 1ms)

*1) K7M-DR10S (/DC), K7M-DT10S: Built-in RS-232C and RS-485 port. Simultaneous use is not allowed and a communication module is not available to use. Built-in Cnet dip switch: ON (RS-232C), OFF (RS-485)

 