Search

LS일렉트릭(주)

LS일렉트릭(주)

LS일렉트릭(주)

LS일렉트릭(주)

1544-2080
기업찾기LS일렉트릭(주)
1/1
LS일렉트릭(주)

LS일렉트릭(주)

Measurement

모델명

시리즈

Protection/Measurement/Meter (Device)


구매 안내

아래는 참고용 정보이므로 세부 조건은 반드시 제조사/판매자에게 문의 바랍니다.

결제 방법

제조사/판매자에게 문의 바랍니다.

납기 정보

제조사/판매자에게 문의 바랍니다.

배송 정보

제조사/판매자에게 문의 바랍니다.

원산지

제조사/판매자에게 문의 바랍니다.


1544-2080

제품 상세 설명

GIMAC-V

Premium multifunction digital integrated metering and control device - Color graphic Touch LCD type.

 

Features

Measurement Function

ㆍHigh precision measurement of various measurement elements (35 elements)

ㆍExtended power quality measurement (63th, THD, TDD, K-factor, Crest factor)

ㆍEvent recording (20~1024 samples)

ㆍSelect Before Operating (SBO) Function

ㆍAutomatic Power Factor Control (APFC) (optional)

ㆍTransient wave and event measurement

 

Convenience Function

ㆍColor touch graphic LCD

ㆍLanguage and user selection menu

ㆍManager software for PC connection

ㆍStatistics and trends for measurement elements

ㆍAdd-ons

 

Communication Function

ㆍVarious communication functions (3 ports)

 

Measurement

Type Measuring item Datiled measuring item Accuracy
Voltage (V) Line voltage Vab, Vbc, Vca, Vlavg Note 0.2%
Phase voltage Va, Vb, Vc, Vnavg 0.2%
Normal, reversed-phase voltage V1, V2 -
Crest Factor Vab, Vbc, Vca, Va, Vb, Vc -
Current Phase current Ia, Ib, Ic, Iavg 0.2%
XPhase current Ix 0.2%
Normal, reversed-phase currents I1, I2 -
Crest Factor Ia, Ib, Ic -
Phase Line voltage ∠Vab, ∠Vbc, ∠Vca 0.5°
Phase voltage ∠Va, ∠Vb, ∠Vc 0.5°
Phase current ∠Ia, ∠Ib, ∠Ic, ∠Ix 0.5°
Electricity Active power Pa, Pb, Pc, ΣP 0.5class
Reactive power Qa, Qb, Qc, ΣQ 0.5class
Apparent power Sa, Sb, Sc, ΣS 0.5class
Electricity energy Active energy WHa, WHb, WHc, ΣWH 0.5class
Reactive energy VARHa, VARHb, VARHc, ΣVARH 0.5class
Reverse active energy rWHa, rWHb, rWHc, ΣrWH 0.5class
Reverse reactive energy rVARHa, rVARHb, rVARHc, ΣrVARH 0.5class
Apparent energy VAHa, VAHb, VAHc, ΣVAH 0.5class
freq Frequency F(Hz) 0.1%
Power Factor Power Factor(PF) Power Factor Power Factor(PF) PFa, PFb, PFc, ΣPF phase phase accuracy
1st harmonic power factor (DPF) DPFa, DPFb, DPFc, ΣDPF
Harmonics Line voltage Vab, Vbc, Vca 2~63th Harmonics -
Phase voltage Va, Vb, Vc 2~63th Harmonics  
Phase current Ia, Ib, Ic 2~63th Harmonics -
THD Vab, Vbc, Vca, Va, Vb, Vc, Ia, Ib, Ic  
TDD Ia, Ib, Ic  
K-FACTOR Ia, Ib, Ic  
AI 4~20mA AI01, AI02 0.5%

Note : Average of line voltage

 

APEC

Type APEC
BANK setting BANK number 0-8
Alarm number 0-1
Capacitor capacitance setting None ~ 999MVA
Alarm contact setting Setting one of extra contact out of DO_01~DO_08
Capacitor closing delay time 10~300sec / 1sec
Dead time (time for charge or discharge) 10~300sec / 1sec
Maximum power factor setting 0.95~1~ -0.90 ( - : indicating lead phase)
Minimum power factor setting 0.80 ~ 0.95
Alarm power factor setting (Alarm occurred) 0.00 ~ 0.90
Event occurrence
Under Voltage
and control Over PF
Low Current Set whether to get EVENT occurred or set the control in case the average current of 3 phase is 1A
Under Voltage Set whether to get EVENT occurred or set the control in case phase voltage ( 3 phase 3 wire, open delta, line voltage)
Over PF Set whether to get EVENT occurred or not when over Max. PF
Under PF Set whether to get EVENT occurred or not when over Min. PF
Over Volt THD Set whether to get EVENT occurred and BANK control or not when THD is above the setpoint
Power Factor control Automatic control Auto
Manual control Manual
Combination control In case all capacitances are set
Circulation control Capacitor In case capacitances are not set - Opening the closed one first and closing the opened last

 

Specification

※ Avoid places with vibration, shock, dust, moisture, corrosive, gas, etc.

문의하기