Electronic Motor Protection Relay

모델명

시리즈

Low Voltage (Device)


구매 안내

아래는 참고용 정보이므로 세부 조건은 반드시 제조사/판매자에게 문의 바랍니다.

결제 방법

제조사/판매자에게 문의 바랍니다.

납기 정보

제조사/판매자에게 문의 바랍니다.

배송 정보

제조사/판매자에게 문의 바랍니다.

원산지

제조사/판매자에게 문의 바랍니다.


1544-2080

제품 상세 설명

IMC-III

Programmable intelligent motor protection device applicable to various motor starting methods.

 

Features

Protection Function

ㆍVarious protection factor for motor (8 protection factors)

ㆍApplicable to invertor circuits

ㆍInstantaneous power failure compensation and restart

ㆍDigital meter function

 

Convenience Function

ㆍEase of installation

ㆍWide current range

ㆍFunction to save fault value and cause

ㆍSelf-diagnosis and sequence monitoring

ㆍTotal operating time and operating time setting

 

Communication Function

ㆍVarious communication compatibilities (RS485 modbus and 4~20mA output)

 

Protection factor

Rating Operating condition Time Remark
Over
current
Inverse Over 110% setting current 1~60s/1s 600% standard operating time
Definite time Over 105% setting current 1~60s/1s Delay time 1~200s
Phase fault Over 70% current phase unbalance Within 1.5s Phase fault rate = Maximum Phase Current - Minimum Phase Current / Maximum Phase Current ×100%
Phase unbalance Current phase unbalance 30~50% Within 5s
Reverse phase Reverse the current phase Within 0.1s Over 110% minimum ratings
Under current Rating current 30~70% Within 3s  
Holding Stall Rating current 150~300% Within 5s Detection after over current setting time
Locked rotor Rating current 200~700% Within 0.5s
Ground fault The current rating 0.1~2.5A setting 0.05~1.0s Ground fault delay operation
Pre-alarm Over 120% setting value   Bar-LED blinking

 

Sequence

Rating Contents
Operating type Direct operation Non-reversible direct operation
Y-▵ operation Y operation time 1~120s/1s
Y-▵ switching time 0.05, 0.1, 0.2s
Forward / Reverse operating Reversible direct operation
Reactor Reactor time 1~120s/1s
Inverter Inverter delayed time ON 1sec/0.1sec
Instantaneous
under voltage
compensation
Compensation time OFF 1~10s /1s
Re-operation delay time 0~300s /1s
Under voltage detection (Rating control voltage × 65%) ± 10%
Re-operation delay time (Rating control voltage × 75%) ± 10%
Remote control Local LOP(Local Operation Panel)
MCC Motor Control Center
Auto PLC, DDC, DCS auto operation
Remote Modbus/RS-485 communication

 

Specification

* D-Time(Delay time) : It is delay time for IMC-IIIa start during motor start time

* O-time (Operating delay time) : When over current generates more then setting current, that makes it delayed until IMC-IIIa operated.