Fire fighting valve manufacturer, Water flow device, Sprinkler head, Various valve and more
■ Specification
ALARM CHECK VALVE
SAV-71
SAV-72
WORKING PRESSURE
1.5kg/cm²~10kg/cm² (Max.14kg/cm²)
1.5kg/cm²~10kg/cm² (Max. 22kg/cm²)
APPLICABLE TEMPERATURE
5~80℃
INSTALLATION METHOD
종형(Vertical)
MIN. OPERATION PRESSURE
1.5kg/cm²
CONNECTION METHOD
KS 10K FF Flange
KS 16K FF Flange (20K 겸용)
HYDRO. TEST PRESSURE
20kg/cm²-2min
32kg/cm²-2min
METERIALS
BODY, COVER
GC 200
GCD 450
SEAT RING
BC 6
DISC RUBBER
N.B.R
■ Dimension
PRESSURE
SIZE
SPACE
VALVE FLANGE
Weight (kg)
L
L1
L2
L3
L4
L5
H
P.C.D
øD
t
n-øh
10K
65
220
170
185
143
145
160
400
140
175
22
4-19
19
80
150
8-19
21
100
240
180
200
155
420
210
24
31
125
260
190
250
8-23
36
280
270
206
440
26
49
16KA
224
25
246
225
33
265
8-25
38
285
230
305
28
12-25
51