Search

LS ELECTRIC

LS ELECTRIC

LS ELECTRIC

LS ELECTRIC

HomeManufacturersLS ELECTRIC
1/1
LS ELECTRIC

LS ELECTRIC

Protection

Model

Series

Protection/Measurement/Meter (Device)


Transaction Process

Please contact Komachine.

Payment

Please contact Komachine.

Delivery

Please contact Komachine.

Shipment

Please contact Komachine.

Origin

Please contact Komachine.


Description

XGIPAM

Next generation digital power protection monitoring system for highly reliable plant facilities.

 

Features

Protection Function

ㆍVarious protection factors (29 protection factors)

ㆍEvent and fault recording (max 1,000 recording)

ㆍVarious measurements and monitoring functions (25 measurements)

ㆍTrip logic and PLC function

ㆍMimic diagram function

ㆍAdvanced power quality measurements (2~63rd harmonic)

ㆍSelect & check before operating (CBO) functions

ㆍVector diagram

ㆍTime characteristic curve

ㆍTrip circuit supervision (TCS) & trip relay supervision (TRS)

ㆍSequence of events (SOE)

ㆍHarmonic spectrum

ㆍAnalog input (optional)

ㆍInput/output points monitoring and control function

ㆍSupervision of CB capacity limit

ㆍBay controller function

ㆍArc protection module (optional)

 

Convenience Function

ㆍEasy connecting to PC manager

ㆍEasy setting group

ㆍFlexible modular architecture hardware and software

ㆍ8.4″ inches of large color touch screen

ㆍLanguage selection and user selective menu (eng/kor)

 

Communication Function

ㆍVarious communication compatibilities

ㆍCommunication redundancy

ㆍIEC61850 communication

 

Protection factor

Type Usage Protection
XGIPAM-F Feeder/Incomming OCR(50/51), OCGR(50/51N), UVR(27), OVR(59), SGR(67G), DGR(67N), OVGR(64I/D), NSOVR(47N), POR(47), SYNC Check(25),
Reclosing(79), Temperature(38)
XGIPAM-B Bay Controller OCR(50/51), OCGR(50/51N), UVR(27), OVR(59), SGR(67G), DGR(67N), OVGR(64I/D), NSOVR(47N), POR(47), 
SYNC Check(25), Reclosing(79), Temperature(38), DOCR(67I/D), NSOCR(46I/D), UFR(81U), OFR(81O), DPR(32P), DQR(32Q)
XGIPAM-M Motor OCR(50/51), OCGR(50/51N), UVR(27), OVR(59), SGR(67G), DGR(67N), OVGR(64I/D), NSOVR(47N), POR(47), Temperature(38), 
Stall/Locked Rotor(48/51LR), THR(49), DOCR(67I/D), UCR(37), NCH(66), NSOCR(46I/D)
XGIPAM-T Transformer OCR(50/51)*2,OCGR(50/51N),UVR(27),OVR(59),Temperature(38),DPR(32P),DFR(87T)
XGIPAM-DG Distributed
Generator
OCR(50/51), OCGR(50/51N), UVR(27), OVR(59), DPR(32P), UPR(37P), DQR(32Q), UFR(81U), OFR(81O), DGR(67N), 
SYNC Check(25), DOCR(67I/D), NSOCR(46I/D), POR(47), NSOVR(47N), ROCOF(81R), SGR(67G), OVGR(64I/D)
XGIPAM-3wT Transformer
(3 wires)
OCR(50/51)×3, OCGR(50N/51N), UVR(27), OVR(59), OVGR(64I/D), DFR(3W87T)

 

Specification

Rating Specification
Wiring   3P3W, 3P4W
Input Frequency   60Hz/50Hz
Voltage   PT: 100/ √3, 110/ √3, 120/ √3, 190/ √3, 100, 110, 120V
  GPT: 100~190V
Current   CT: 5A, ZCT: 1.5mA
Power consumption   Standby: Max. 30W, Operating: Max. 70W
Control voltage   AC110V/DC110~125V, 50/60Hz 
Burden   PT: Max. 0.5VA(Phase PT Standard), CT: Max. 1.0VA
Output contact TRIP Rated   AC 250V 10A / DC 30V 10A, Resistive Load
Open   AC 2500VA, DC 300W
ALARM Rated   AC 250V 5A / DC 30V 5A, Resistive Load
Open   AC 1250VA, DC 150W
Insulation Resistance   Over DC 500V 10㏁
Dielectric strength   AC 2kV(1kV) / for 1 min
Overload withstand Current circuit   Twice the rated current is no problem after 3hours of application.
  20 times of the rated current is no problem when applied for 2seconds.
Voltage circuit   1.15times of rated voltage is no problem after 3hours of application
Fast Transient Disturbance   Power Input 4kV, DI/DO input 2kV, Other Input 1kV
Electrostatic Discharge(ESD)   Air 8kV, Contact 6kV
Operation temperature   -10℃ ~ 55℃
Storage temperature   -25℃ ~ 70℃
Humidity   Within 80% RH, no condensation
Altitude  1500m or less
Others  No vibration and shock, no air pollution
Standard   IEC 60255-22-1: 1MHz Burst disturbance tests
  IEC 60255-22-2: Electrostatic discharge tests
  IEC 60255-22-3: Radiated radio frequency electromagnetic field
  IEC 60255-22-4: Electrical fast transient/burst immunity test
  IEC 60255-22-5: Surge immunity test
  IEC 60255-22-6: Immunity to conducted disturbances induced by radio frequency fields
  IEC 60255-22-7: Power frequency immunity test
  IEC 60255-11: Interruptions to and alternating component (ripple) in d.c. auxiliary quantity of measuring relay
  IEC 60255-25: Electromagnetic emission tests for measuring relays and protection equipment
  KEMC 1120
  IEC 6850-6,7-1,7-2,7-3, and 8-1
Weight   7 kg (HMI: 2kg)

Download

Catalog-LS ELECTRIC-Protection-XGIPAM

Inquiry

Komachine Inc.
Head Office:
Ace Dongbaek Tower 1-1101, 16-4,
Dongbaekjungang-ro 16beon-gil, Giheung-gu,
Yongin City, Gyeonggido, South Korea 17015
Branch Office:
606, Seoul Stratup Center, 10,
Noryangjin-ro, Dongjak-gu, Seoul, South Korea 06938
CEOCharlie Park
Corporate #535-86-00664

ⓒ2024 Komachine Inc. All rights reserved.