Search

KOREA KOSO

KOREA KOSO

KOREA KOSO

KOREA KOSO

HomeManufacturersKOREA KOSO
1/1
KOREA KOSO

KOREA KOSO

Motorized Actuators

Model

Series

Actuators


Transaction Process

Please contact Komachine.

Payment

Please contact Komachine.

Delivery

Please contact Komachine.

Shipment

Please contact Komachine.

Origin

Please contact Komachine.


Description

▶ 3100R/3200R/3300R/3400R/3400L/3420R/3420L/3900R: Motorized Actuators



Here is a line-up of motor-operated actuators of basically ON/OFF control. 3100 series is featured by small-size, lightweight and high output. 3400 series and 3420 series use case, cover, mounting portion, etc. commonly with a full-electronic actuator.

3900 series can be used for an inexpensive and simple instrumentation, with a potentiate mounted for detection of control position, besides small size and lightweight. Explosion-proof approved models are also replete. 




Specification


3100R Rotary stem motion type

Principal uses

2-position control

Power

Drive motor

Synchronous motor

Power supply

Single phase 100/110/200/220V AC 50/60 Hz

Motor rating

10 minutes

Control mechanism

Input signal

Switching contact

Ancillary mechanism

Overload protection

With built-in thermal protector

Space heater

- Optional

5W

Conditions for installation

Ambient temperature

-10 to 50°

Ambient temperature

- With space heater

-20 to 40°

Mounting position

Should not be mounted in an inverted position from the maintenance face.

Body portion

External sheath type

Protection class IP65 or equivalent

Wiring port

G1/2 (1 place)

Wiring port

- Optional

Various adaptors can be mounted

Installation seat

Conforms to ISO





3200R Rotary stem motion type

Principal uses

2-position control

Power

Drive motor

AC reversible motor

Power supply

Single phase 100V AC 50/60Hz

Power supply

- Optional

Single phase 110/200/220V AC 50/60Hz

Motor rating

30 minutes

Control mechanism

Input signal

Switching contact

Opening signal transmission

- Optional

Potentiometer (5kΩ/135Ω)

Ancillary mechanism

Control position detection

- Optional

Auxiliary limit switch (voltfree), maximum points of detection 2 places

Overload protection

With built-in thermal protector

Space heater

- Optional

* Please contact us for details, as this matter depends on the power supply voltage.

Conditions for installation

Ambient temperature

-10 to 50°

Ambient temperature

- With space heater

-20 to 40°

Mounting position

Should not be mounted in an inverted position from the maintenance face.

Body portion

External sheath type

Protection class IP65 or equivalent

Wiring port

G1/2 (1 place)

Wiring port

- Optional

Various adaptors can be mounted

Installation seat

Conforms to ISO





3300R Rotary stem motion type

Principal uses

2-position control / Endless control / Multi-revolution control

Power

Drive motor

AC reversible motor

Power supply

Single phase 100V AC 50/60Hz

Motor rating

30 minutes

Control mechanism

Input signal

Switching contact

Input signal

- With control pack

4 to 20mA DC or 1 to 5V DC

Opening signal transmission

- Optional

Potentiometer (5KΩ/135Ω)

Ancillary mechanism

Control position

detection-Optional

Auxiliary limit switch (voltfree), maximum points of detection 2 places

Dismountable handle type,

wit clutch- Optional

Dismountable handle type, wit clutch

Overload protection

With built-in thermal protector

Space heater

- Optional

* Please contact us for details, as this matter depends on the power supply voltage.

Control

- Optional

Control pack (endless type cannot be mounted)

Conditions for installation

Ambient temperature

-10 to 50°

Ambient temperature

- With space heater

-20 to 40°

Mounting position

Should not be mounted in an inverted position from the maintenance face.

Body portion

External sheath type

Protection class IP55 or equivalent

Wiring port

G1/2 (1 place)

Wiring port

- Optional

Various adaptors can be mounted,

Terminal box

Installation seat

Conforms to ISO





3400R Rotary stem motion type/3400L Linear stem motion type

Principal uses

2-position control

Power

Drive motor

AC reversible motor

Power supply

Single phase 100V AC 50/60Hz

Power supply

- Optional

Single phase 110/200/220V AC 50/60Hz

Motor rating

30 minutes

Control mechanism

Input signal

Switching contact

Opening signal transmission

- Optional

Potentiometer (5KΩ/135Ω)

Ancillary mechanism

Control position detection

- Optional

Auxiliary limit switch (voltfree), maximum points of detection 2 places

Dismountable handle type

Dismountable handle type

Overload protection

With built-in thermal protector

Overload protection

- Optional (3400R)

Torque switch on closed side (CW direction only)

Space heater

- Optional

* Please contact us for details, as this matter depends on the power supply voltage.

Conditions for installation

Ambient temperature

-10 to 50°

Ambient temperature

- With space heater

-20 to 40°

Mounting position

Should not be mounted in an inverted position from the maintenance face.

Body portion

External sheath type

Protection class IP55 or equivalent

Wiring port

G3/4 (3400R) G1/2 (3400L) 2 places

Wiring port

- Optional

Various adaptors can be mounted

Terminal box (3400L)

Installation seat

Conforms to ISO





3420R Rotary stem motion type/3420L Linear stem motion type

Principal uses

2-position control

Power

Drive motor

AC reversible motor

Power supply

Single phase 100/110V AC 50/60Hz (+/- 5%)

Power supply

- Optional

Single phase 200/220V AC 50/60Hz (+/- 5%)

Motor rating

30 minutes

Control mechanism

Input signal

Switching contact

Opening signal transmission

- Optional

Potentiometer (5KΩ/135Ω)

Ancillary mechanism

Control position detection

- Optional

Auxiliary limit switch (voltfree), maximum points of detection 2 places

Dismountable handle type

With handle insertion hole

Overload protection

With built-in thermal protector,

Torque switch (3420R is an option)

Space heater

- Optional

* Please contact us for details, as this matter depends on the power supply voltage.

Conditions for installation

Ambient temperature

-10 to 50°

Ambient temperature

- With space heater

-20 to 40°

Mounting position

Should not be mounted in an inverted position from the maintenance face.

Body portion

Wiring port

G1/2 (2 places)

Wiring port

- Optional

Various adaptors can be mounted

Terminal box

Installation seat

Conforms to ISO





3900R Rotary stem motion type

Principal uses

2-position control

Power

Drive motor

AC reversible motor

Power supply

Single phase 100/110V AC 50/60Hz (+/- 5%)

Power supply

- Optional

Single phase 200/220V AC 50/60Hz (+/- 5%)

Motor rating

30 minutes

Control mechanism

Input signal

Switching contact

Opening signal transmission

- Optional

Potentiometer (1KΩ/135Ω)

Ancillary mechanism

Control position detection

- Optional

Auxiliary limit switch (voltfree), maximum points of detection 2 places

Dismountable handle type

With handle insertion hole

Overload protection

With built-in thermal protector

Space heater

- Optional

* Please contact us for details, as this matter depends on the power supply voltage.

Conditions for installation

Ambient temperature

-10 to 50°

Ambient temperature

- With space heater

-20 to 40°

Mounting position

Should not be mounted in an inverted position from the maintenance face.

Body portion

External sheath type

Protection class IP65 or equivalent

Wiring port

G1/2 (2 places)

Wiring port

- Optional

Various adaptors can be mounted,

Terminal box

Installation seat

Conforms to ISO

Inquiry

Komachine Inc.
Head Office:
Ace Dongbaek Tower 1-1101, 16-4,
Dongbaekjungang-ro 16beon-gil, Giheung-gu,
Yongin City, Gyeonggido, South Korea 17015
Branch Office:
606, Seoul Stratup Center, 10,
Noryangjin-ro, Dongjak-gu, Seoul, South Korea 06938
CEOCharlie Park
Corporate #535-86-00664

ⓒ2024 Komachine Inc. All rights reserved.