JRV-SF21 (Pilot Operating Type)
As it is a pilot type, it does not require an auxiliary power source such as compressed air or electricity and has a larger capacity compared to the direct impingement type. There is a wide range of pressure adjustment available. With the built-in "pressure relief valve filter" with a practical design patent No.13137, errors caused by the scale or impurities inside the pipes are prevented. Compatible with disks/ sheets. Leakage: Less than 0.05% of the standard flow
Product specification
| MODEL |
FORMAT |
APPLICABLE LIQUIDS |
CORRECT TEMPERATURE TO BE APPLIED |
CORRECT PRESSURE TO BE APPLIED MPA (KGF/CM²) |
MAXIMUM PRESSURE REDUCTION RATE |
MINIUM DIFFERENCE IN PRESSURE MPA (KGF/CM²) |
HOW TO CONNECT THE PRODUCT |
MATERIAL |
| JRV-SF21 |
Pilot type |
Steam |
Max.300 |
Primary side |
Secondary side |
10:1 |
0.07(0.7) |
JIS B 2220 10K,20K RF Ranged |
Main body |
Key part |
2.0 Lower than 20 (20.0) |
0.035~1.6 (0.35~16.0) |
Cast Steel |
Stainless Steel |
※ Make adjustments so that the pressure on the secondary side is 80% or lower than the primary side pressure.