Search

LS ELECTRIC

LS ELECTRIC

LS ELECTRIC

LS ELECTRIC

HomeManufacturersLS ELECTRIC
1/1
LS ELECTRIC

LS ELECTRIC

PLC (XGB Series) XBC/XEC H-Type

Model

Series

PLC (Smart Automation Solution)


Transaction Process

Please contact Komachine.

Payment

Please contact Komachine.

Delivery

Please contact Komachine.

Shipment

Please contact Komachine.

Origin

Please contact Komachine.


Description

Feature

Various expansion

ㆍMax. 384 I/O points

ㆍMax. 2 communication modules

ㆍRS-232C, RS-422/485, Ethernet, CANopen, Profibus-DP, DeviceNet, EtherNet/IP, RAPIEnet

 

Powerful & various built-in functions

ㆍCnet 2 ports

ㆍHigh-speed counter

ㆍPositioning (Tr. type only)

 

High performance type

Performance Specifications

Item XBC/XEC-DR32H XBC-DR32H/ DC*1) XEC-DR32H / DI XBC/XEC-DN32H XEC-DP32H*1) XBC-DN32H / DC XBC/XEC-DR64H XBC-DR64H/ DC*1) XEC-DR64H / DI XBC/XEC-DN64H XEC-DP64H*1) XBC-DN64H / DC
Control method Repetitive, cyclic, interrupt, constant scan
I/ O control method Refresh mode (Batch processing by scan synchronization), Direct mode by instruction
Programming language Ladder diagram or IEC standard (LD, SFC, ST)*1)
Processing speed 83 ns / Step
Program capacity 15Kstep (IEC type: 200KB)
Main unit I /O points 32
(Input:16, Output:16)
32
(Input:16, Output:16)
64
(Input: 32, Output: 32)
64
(Input: 32, Output: 32)
Max. I /O points
(Main + Expansion 10 stages)
352 points 384 points
Total program 128
Operation mode RUN, STOP, DEBUG
Self diagnosis Detects errors of scan time, memory error, I/O error, battery error, power error, etc.
Program port USB (Rev 1.1), RS-232C 1 channel (Loader)
Retain data at power failure Latch area setting at basic parameter
Built-in functions RS-232C / RS-485 (2 ch), Pulse catch, Input filter, External interrupt, PID control, High-speed counter, Positioning, RTC
Data memory
XBC XEC (IEC type)
P P0000 ~ P1023F (16,384 points) Symbolic variable A 32KB (Max. 16KB retain setting available)
M M0000 ~ M1023F (16,384 points) Input variable I 2KB (%IX 15.15.63)
K K0000 ~ K4095F (65,536 points) Output variable Q 2KB (%QX 15.15.63)
L L0000 ~ L2047F (32,768 points) Direct variable M 16KB (Max. 8KB retain setting available)
F F0000 ~ F1023F (16,384 points) R 20KB (1 block)
T 100ms, 10ms, 1ms: T0000 ~ T1023
(1,024)(Adjustable by parameter setting)
W 20KB
C C0000 ~ C1023 (1,024) Flag variable F 2KB
S S00.00 ~ S127.99 K 8KB
D D0000 ~ D10239 (10,240 word) L 4KB
U U00.00 ~ U0A.31
(Analog data refresh area: 352 word)
N 10KB
Z Z000 ~ Z127 (128 word) U 1KB
N N000 ~ N5119 (5,120 word) Flash area R 20KB (2 blocks)

*1) XEC is IEC standard language programming.

 

Input specification

Item XBC/XEC- DR32H XBC/XEC-DN32H XEC-DP32H XBC/XEC- DR64H XBC/XEC-DN64H XEC-DP64H XEC-DR32H / D1
XEC-DR64H / D1
Input points 16 points 32 points 16 points
Rated input voltage DC 24V DC 12 / 24V
Rated input current 4mA (Contact 0~7: 9mA) 5 /10mA (Contact 0~7 : 7/15mA)
Operation voltage range DC 20.4 ~ 28.8V (Ripple rate < 5%) DC 9.5~30V (Ripple rate < 5%)
On voltage / On current DC 19V or more/3mA or more DC 9V or more/3mA or more
Off voltage / Off current DC 6V or less/1mA or less DC 5V or less/1mA or less
Input resistance 5.6k Ω (P00 ~ P07: 2.7k Ω ) 2.7k Ω (%IX0.0.0~%IX0.0.7:1.8k Ω )
Response time Off → On 1/3/5/10/20/70/100 ms
(Setting by CPU parameter) Initial value: 3ms
On → Off

 

Relay output specification

Download

Catalog-LS ELECTRIC-PLC (Smart Automation Solution)-PLC XGB Series catalog

Inquiry

Komachine Inc.
Head Office:
Ace Dongbaek Tower 1-1101, 16-4,
Dongbaekjungang-ro 16beon-gil, Giheung-gu,
Yongin City, Gyeonggido, South Korea 17015
Branch Office:
606, Seoul Stratup Center, 10,
Noryangjin-ro, Dongjak-gu, Seoul, South Korea 06938
CEOCharlie Park
Corporate #535-86-00664

ⓒ2024 Komachine Inc. All rights reserved.