GIMAC-IV

Premium multifunction digital integrated metering and control device - 20x4 LCD type.

 

Features

Measurement Function

ㆍHigh precision measurement of various measurement elements (27 elements)

ㆍExtended power quality measurement (63th, THD)

ㆍEvent recording (300 samples)

ㆍSelect Before & Check Before Operating (CBO) functions

ㆍImproved precision through a digital filter

ㆍAnalog input (2 points, optional)

ㆍCapacitor bank (8 banks)

ㆍOptimal power factor control

ㆍEfficient maximum demand power management

ㆍAutomatic Power Factor Control (APFC), (optional)

 

Convenience Function

ㆍVarious self-diagnosis functions

 

Communication Function

ㆍVarious communication functions (1 ports)

 

Measurement

Model Measurement Display range Accuracy Remarks
GIMAC-415 Current, I 0.000A ~ 999.99kA ±0.2% Ia, Ib, Ic, In
Voltage, V 0.000V ~ 999.99kV ±0.2% Va, Vb, Vc, Vab, Vbc, Vca
Active power, Watts 0.000W ~ 99999.9MW ±0.5% + : Forward
- : Reverse
Reactive power, Var 0.000Var ~ 99999.9MVar ±0.5%
Apparent power, VA 0.000VA ~ 99999.9MVA ±0.5%
Active energy, Wh 0.000Wh ~ 99999.9MWh ±0.5%
Reactive energy, Varh 0.000Varh ~ 99999.9MVarh ±0.5%  
Frequency, F 45 ~ 70Hz ±0.05Hz  
Power factor, PF -1.000 ~ 1.000 ±0.5% cosø (+ : Lag, - : Lead)
Phase 0.000。~ 360.00。 ±0.5。  
Normal current, I1 0.000A ~ 999.99kA    
Reverse phase current, I2 0.000A ~ 999.99kA    
Zero phase voltage, Vo 0.000V ~ 999.99kV ±0.5% Vo, Vo_max
Normal voltage, V1 0.000V ~ 999.99kV    
Reverse phase voltage, V2 0.000V ~ 999.99kV    
Unbalanced factor 0.000 ~ 100.00%    
Harmonics I 0.000A ~ 999.99kA   2nd ~63th
Harmonics V 0.000V ~ 999.99kV   2nd ~63th
Demand I 0.000A ~ 999.99kA   Peak demand
Demand W 0.000W ~ 99999.9MW   Peak demand
AI (Analog Input) DC 4.000 ~ 20.00mA ±0.5%  

 

Specification

Type Specification
Wirings  1P2W, 1P3W, 3P3W, 3P4W
Input Frequency  50Hz/60Hz
Voltage PT  10~230V
GPT  2.2~230V
Current CT  0.05~6A
Control Voltage   AC/DC 110V or AC/DC 220V
Power Consumption  Max. 30W
Burden PT  Max. 1.0VA
CT  Max. 1.0VA
Input contact 10EA   Digital Input : AC/DC 110V or AC/DC 220V
Output contact 2EA for power  AC 250V 16A/DC 30V 16A
 3840VA/480W
8EA for alarm  AC 250V 16A/DC 30V 16A
 3840VA/480W
Insulation Resistance  Over DC 500V 100㏁
Insulation Voltage   AC 2kV (1kV) / for 1 min
Impulse Voltage   AC 5kV (3kV) Over 1.2×50㎲
Overload Withstand Current circuit  1.2 In for 3 hours
 8 In for 2 seconds
Voltage circuit  1.15 Vn for 3 hours
Fast Transient/Burst Immunity   Power Input 4kV (PT, CT)
 Other Input 2kV (Analog Input 1kV)
ESD (Electrostatic Discharge)   Air 8kV
 Contact 6kV
Operation temperature   -10℃ ~ 55℃
Storage Temperature   -25℃ ~ 70℃
Humidity   Within 80% RH, no condensation
Altitude   2000m and below
Others   Non-impact place
 Non-air pollution place
Standard  IEC 60255, IEC61000-4, KEMC 1110
Communication  MODBUS/RS485, DNP3.0
Dimension (W×H×D)  190×255×116 (mm)
Weight  3.6kg

Download

Manual-LS ELECTRIC-Measurement-GIMAC-IV

Inquiry

Komachine Inc.
Head Office:
Ace Dongbaek Tower 1-1101, 16-4,
Dongbaekjungang-ro 16beon-gil, Giheung-gu,
Yongin City, Gyeonggido, South Korea 17015
Branch Office:
606, Seoul Stratup Center, 10,
Noryangjin-ro, Dongjak-gu, Seoul, South Korea 06938
CEOCharlie Park
Corporate #535-86-00664

ⓒ2024 Komachine Inc. All rights reserved.